Telecom Outdoor UPS IP65-1KW Edge Span U1000-DC
1KW Outdoor UPS Power Backup Enclosure for Telecom High Reliability Scenario
Outdoor UPS IP65-1KW Edge Span U1000-DC
Telecom Outdoor UPS IP65-1KW Edge Span U1000-DC is an outdoor UPS system designed for Telecom high reliability scenarios. The whole system power is 1KW, suitable for use in Telecom 48VDC voltage scenarios. For example, deployment scenarios such as Small Cell Backup Power Supply, Transmission Site Battery Backup Power Supply, and industrial control power supply. For outdoor scenarios, the entire system is designed with IP65 ingress protection, and the entire casing is a cast aluminum shell design that is completely rust-proof to match the high reliability and low maintenance cost requirements of Telecom scenarios. Compared with traditional fan-based UPS systems, the entire Edge Span U1000 system uses natural heat dissipation. Because there is no fan, the whole system can run maintenance-free for years. The core power system of the Edge Span U1000 outdoor UPS IP65 uses a 1KW rectifier with an efficiency of more than 95%, and the circuit is designed to be resistant to high temperature in outdoor high temperature environments. Unlike general outdoor UPS batteries that are plug-in, Edge Span U1000 designs batteries, monitoring, and UPS into an all-in-one system, thereby simplifying customer site deployment. The built-in battery can be configured up to 55AH (48V), 2640Wh. The battery can run for 2 hours with a 1000W load. We can also reduce the battery size based on the customer's budget and load conditions to accurately match the scenario. Edge Span U1000 supports two installation methods: UPS pole mount and UPS wall mount.
Features of Outdoor UPS IP65 Edge Span U1000
IP65/NEMA4X
IP65/NEXMA4X level ingress protection matches the Telecom network’s requirements for system stability, preventing the intrusion of external water and dust from affecting system reliability.
Outdoor Optimized Rugged Design
Following the complex environment in which Telecom equipment is deployed, the shell of Outdoor UPS IP65 Edge Span U1000 is designed to be impact-resistant and corrosion-resistant. Its protection level reaches IK08. This greatly protects the system in complex working environments.
Rust-Proof for Long Term Operation
In order to achieve the best rust-proof effect, the shell of outdoor UPS IP65 is made of cast aluminum. Aluminum is naturally rust-proof, so that the system will not be affected by rain, high humidity, and high salinity environments during long-term operation, thereby achieving the reliability requirements of Telecom level to the greatest extent.
Surge Protection
Surge protection is a basic requirement for outdoor UPS and is greatly enhanced in the design of Edge Span U1000 outdoor UPS IP65. All input and output interfaces of the system are designed with surge protection in mind. Power input and output are protected at 20Ka level, while low voltage interface and signal interface are protected at 6ka level.
Natural Heat Dissipation
Without FAN cooling, the entire outdoor UPS IP65 system adopts natural heat dissipation to solve the cooling problem. Compared with FAN cooling, natural heat dissipation does not have the problem of vulnerable mechanical parts, and can work stably and maintenance-free for a long time, thereby reducing the probability of on-site maintenance and greatly reducing the OPEX of the entire network operation and maintenance.
High Temperature Resistant Long Life Battery
The most vulnerable and core component of the outdoor UPS IP65 is the battery. The battery must be resistant to high temperatures and have a long life. Lithium batteries usually meet these characteristics. Lead-acid batteries are not suitable for outdoor high-temperature environments.
Comprehensive Protection of Input and Output
Outdoor UPS IP65 is deployed outdoors or even in remote areas. The outdoor power grid is very unstable in remote areas of many countries, and there will be over-voltage and under-voltage. In addition, the outdoor UPS output is connected to the load because it is an outdoor device, which is prone to short circuit, overload and other problems caused by factors such as mouse gnawing or line aging. Therefore, we have added comprehensive protection for both input and output in the design, including overvoltage, undervoltage, overcurrent, short circuit and other protections, so that when an abnormality occurs, the outdoor UPS IP65 will not be damaged. At the same time, it also ensures the safety of the load equipment.
High Efficiency and PFC
The outdoor UPS IP65 Edge Span U1000 has an overall efficiency of more than 95% and includes a PFC (Power Factor Correction) function.
System Monitoring
Key components in the Outdoor UPS IP65 Edge Span U1000, such as UPS, battery, control board, surge suppressor, temperature and humidity conditions are monitored and managed, and reported to Edgeware’s software platform Convergence Software Platform. In addition, if the customer has a third-party software platform to manage, we can also report through MQTT.
Outdoor UPS Edge Span U1000-DC
- Industrial level 1000W DC-UPS(110/220VAC Input, DC48V Output)
- Lithium battery 55AH(48V)with 2640Wh can support 1000W load for 2 hours of system autonomy. If necessary, a smaller battery can be configured according to the customer’s load to reduce costs.
- Totally sealed design reaches IP65/NEMA4X ingress protection,dust and water penetration-free system
- 20Ka surge protection with AC Input and DC48V Output
Edge Span U1000 Outdoor UPS Application
Edge Span U1000 outdoor UPS IP65 can be widely used in 4G/5G small cell backup power supply, industrial control and other high-power power backup scenarios. Edge Span U1000 can also configure different monitoring modules according to customer scenarios to send monitoring traffic back to the software platform via Ethernet fiber port or 4G.
Specification of Edge Span U1000 Outdoor UPS IP65
Edge Span U1000 IP65/NEMA4 Outdoor UPS Specification | |
Dimension | W*H*D 295mm*355mm*214mm |
Weight | 14kg(with all system) |
Material | Aluminum |
Ingress Protection | IP65 |
Heat Dissipation | No fan design, natural heat dissipation |
System Operating Temperature | -20~+75°C, 5%~90% RH Non condensing |
DC-UPS | Rated Power 1000W or 2000W Input 110V/220V 50/60Hz Output 42.00-58.00VDC |
Battery | Embedded 48V55AH Lithium Battery Can also configure using external battery pack. |
Network and System Surge Suppression | 20KVA |
Smart Breaker | Remote control power on and off from Edgeware convergence platform 10A 110v/220v Leakage Protection Overvoltage Protection Under Voltage Protection Overcurrent Protection Short circuit Protection Lightning Protection |
Output Power | DC48 2-6 Channels Can be Customized |
System Monitoring and Management | Work with Edgeware Convergence software platform to perform system monitoring and management |
Environment Monitoring | System temperature, humidity. Box open and close status |
UPS Status Monitoring | Input Voltage, Output Voltage Input/Output Power,Rated Power Battery Charge/Discharge Current Input Current, Load Current Normal, Power Grid Off, Fault |
Smart Breaker Monitoring | Remote Control Failure Status Voltage Current Undervoltage Overvoltage Overcurrent Current leakage |
Specification of UPS Module
Input voltage range | Rated Output Voltage | Rated Output Power | Precision Rate | Output Ripple | Battery Recommended |
90~280VAC | 53.5VDC | 1KW | ≤±1% | ≤200mVpp |
Item | Specification | Notes |
Working Temperature | -30℃~+60℃ Full Load | Long Time Operation |
Storage Temperature | -40℃~+70℃ | |
Humidity | 10-95% | No Condensation |
Altitude | 0-4500 meters | |
Atmospheric pressure | 70~106 kpa | |
Cooling | Natural cooling | |
Noise during Operation | < 42dB |
Item | Specification | Notes |
Rated Input Voltage | 90-280VAC |
|
Max Input Current | 20A |
|
Input Impulse current | 40A |
|
Undervoltage Protection | 200VDC/85VAC | 1s System in Protection |
Overvoltage Protection | 410VDC/300VAC | |
Undervoltage Recovery | 220VDC/100VAC | 5s Delay System Recovery from Protection |
Overvoltage Recovery | 405VDC/295VAC |
Item | Specification | Notes |
Rated Output Voltage | 53.50 VDC | In lead-acid battery mode, standard float voltage |
Output Voltage Range | 42.00-58.00VDC | Monitoring adjustment, automatic adjustment of floating charge |
Rated Output Power | 1KW | The current limiting and power limiting parameters during power operation will automatically adjust with changes in voltage and temperature. |
Rated Output Current | 10.4A | |
Max Output Current | 1.20In(Hardware Constant Current Control) | |
Efficiency | ≥94% | |
Source Adjustment Rate | ≤±1% | |
Load Regulation Rate | ≤±0.6% | |
Output Ripple and Noise | ≤200mV | Rated input, full load output, bandwidth limited to 20MHz |
Shutdown Hold Time | ≥10mS | |
Switch On/Off Overshoot Range | ≤±5% | |
Switch On Output Delay | 3-8s | |
Dynamic Response Overshoot | △V:≤±5% | 25%~50%~25% or 50%~75%~50% |
Dynamic Response Recovery Time | ≤200uS | |
Output Undervoltage Protection | < 30V | When system go into protection, delay 30S to restart。 |
Output Overvoltage Protection | > 62V | System Locked; power off and restart to unlock. |
Output Overcurrent Protection | ≥1.1In,last 30s protection | When system go into protection, delay 30S to restart。 |
Output Short Circuit Protection | Hardware current limit,0.2s system switch off | |
Over Temperature Protection | Switch based on temperature plus software over temperature protection |
Item | Test Condition | Notes | ||
Anti-Electricity Strength | Input to Output | 3000Vac/10mA/1min | No Flashover, No Breakdown | |
Input to GND | 1500Vac/10mA/1min | No Flashover, No Breakdown | ||
Output to GND | 500Vdc/10mA/1min | No Flashover, No Breakdown | ||
Output to Communication Port | 500Vdc/10mA/1min | No Flashover, No Breakdown | ||
Insulation Resistance | Input to Output | ≥10MΩ @ 500VDC | Under normal atmospheric pressure, relative humidity is 90%, when the test DC voltage is 500V | |
Input to GND | ≥10MΩ @ 500VDC | |||
Output to GND | ≥10MΩ @ 500VDC | |||
Leakage Current |
| <3.5mA | Rated Input Voltage | |
Design According Safety Regulation | UL60950 EN60950 | Design meets standard requirements | ||
EMC | CE | CLASS A 6dB lower (or 6dB lower than CLASS A with the system) | CISPR 22(1998), FCC PART 15(2012-05) | |
RE | CLASS A 6dB lower (or 6dB lower than CLASS A with the system) | CISPR 22(1998), FCC PART 15(2012-05) | ||
SURGE | LEVEL 2 B | EN61000-4-5,EN55024 ETSI EN 300 386 V1.3.2 | ||
LEVEL 3 R | EN61000-4-5,EN55024 ETSI EN 300 386 V1.3.2 | |||
EFT | LEVEL 3 (2kV/5kHz) B | EN61000-4-4,EN55024 ETSI EN 300 386 V1.3.2 | ||
ESD | A. Contact Discharge:±6kV/8kV; Air Discharge:±8kV/15kV; B. Number of Discharges: 20 Times for Positive and negative electrodes C. Performance judgment level: B/R | EN61000-4-2,EN55024 ETSI EN 300 386 V1.3.2 | ||
CS | Harassment Intensity:10V Performance Judgment Level: A | EN61000-4-6,EN55024 ETSI EN 300 386 V1.3.2 | ||
RS | Harassment Intensity:10V/m Performance Judgment Level: A | EN61000-4-3,EN55024 ETSI EN 300 386 V1.3.2 |