Edgeware AC/DC Power System ECM45D65B 300A 18KW
Product Description
The ECM45D65A1 embedded power system realizes 6*50A module configuration in a height of 5U, with high reliability, the switch is arranged on the front, and the front wiring is safe to operate, neat and beautiful. Used in high-end professional networks, such as small switching centers, transmission sites, small base stations, and broadband access.
The maximum capacity of the system is 300A. The system is equipped with AC input, battery protection switch and battery power-off function.
Performance
- 19-inch standard width, wide installation adaptability
- Ultra-compact design, 5U height
- Front wiring, front operation, safe and beautiful
- Wide input voltage range, strong grid adaptability
- 5+1 module configuration, high reliability
- With energy-saving sleep function, improve system efficiency
- Wide operating temperature range, strong environmental adaptability
- Rectification and monitoring support hot swap, fast and convenient maintenance
- Provide network port, serial port, dry contact communication interface, easy
- Realize remote monitoring
Mechanics | 19-inch width, 5U height |
Dimension(mm) | 482.0(W)*344.9 (D)*220.6(H) |
Weight(Kg) | ≤15 |
AC input | 3 phase 5 wires 63A/4P |
Battery MCB | 125A/1P×2 |
LLVD breakers | 32A/1P×2+40A/1P×2+63A/2P×3 |
BLVD breakers | 6A/1P×2+10A/1P×2+16A/1P×2 |
Module type | ECMR483000HG1 |
Specification | Description |
AC Input | 85Vac~300Vac |
Power Factor | 0.99 |
Efficiency | >96% |
DC Output | -43Vdc~-58Vdc |
Rated voltage | -48Vdc |
Nominated voltage | -53.5Vdc |
Controller—MC2600, LCD display, RS485 |
Alarm: protection, module fault, AC off, SPD fault, Low battery voltage |
1000 alarms history |
Environment accessing: |
Door check, 4 ways temperature, humidity |
Control function: |
Modules on/off, battery disconnection |
Battery management:: |
Boost/float charge, temperature compensation, battery disconnection, battery self-test, module dormancy |