Edgeware ECM45K1-A3A32 AC/DC Power System-90A 5.22KW
Product Overview
ECM45K1-A3A32 sub-rack power supply, 2U height compact design to meet critical application needs of fiber and microwave transmission, access device, switch. The system maximum power is 90A, with AC/battery/load terminals. The cables are back accessing with terminals.
Performance
- Standard 19-inch width which has the advantage of wide use
- 2U height compact design, space and installation cost can be saved
- Front operation and cable back accessing, good-looking and safe maintenance
- Perfect battery management, prolongs the life of the battery well provide various communication ports, RS232/485, internet port, dry contacts, etc. which enables flexible networking and remote monitoring
- Rectifier and controller are hot pluggable, easy and quick on-line maintenance
- Wide input voltage range(85-300Vac) the power grid is adaptable
Specifications
Type | ECM45K1-A3A32 | |
System | Dimension | 483.6(W)*310.0 (D)*2U(H) |
Weight | ≤15kg (without rectifiers) | |
Cooling mode | Natural cooling | |
Installation mode | Installed on 19-inch rack or inside the cabinet | |
Cabling mode | Back inlet and outlet | |
Maintenance mode | Front maintenance, support module grade change | |
Protection level | IP20 | |
AC Distribution | Input mode | 220VAC single phase |
Input capacity | 1×50A/2P terminal;C63A/2P MCB | |
Input frequency | 45~66Hz, rated value: 50Hz/60Hz | |
DC Distribution | Output voltage | -42~-58VDC, rated value: -53.5VDC |
Maximum capacity | 5.22kW | |
Battery breakers | 2×85A/2P terminals;C63A/1P*2 MCBs | |
Load breakers | BLVD:6×50A/2P terminals | |
Rectifier | Input voltage | 85VAC~300VAC, rated 220VAC |
Efficiency | >92% | |
Rated power | 1740W(176~300VAC) | |
Working temperature | -40℃~+75℃(fully output below 45℃) | |
Dimension | 95.3mm(W)×230.1mm(D)×41.5mm(1U/H) | |
Weight | ≤1.5kg | |
Cooling mode | Forced cooling | |
Power factor | ≥0.99 | |
THD | ≤5% | |
Controller | Signal input | 5 AI(3 Battery temp., ambient temp., ambient humidity) ,7 DI(spd, 6 common DI) |
Alarm output | 6 dry contact | |
Communication port | RS232/485, SNMP | |
Display mode | LCD | |
Environment | Operating temperature | -40℃~+65℃ |
Storage temperature | -40℃~+70℃ | |
Operating humidity | 5%~95%(non-condensing) | |
Altitude | 0~3000m(If the altitude is within the range of 2000m to 3000m, the maximum operating temperature decreases by 1℃ as the altitude increases by 200m.) |