Edgeware Solar Hybrid Power System 24KW
Product Overview
24KW Hybrid System sub-rack power supply, 13U height compact design to meet critical application needs of fiber and microwave transmission, access device, switch. The system maximum power is 24KW, with AC/DC/battery/load MCBs. The cables are front accessing with MCB and busbar.
Specifications
Type | 24KW Hybrid System | |||
System | Dimension | 19 Inch(W)*350.0(D)*13U(H) | ||
Weight | ≤40kg (without rectifiers) | |||
Cooling mode | Natural cooling | |||
Installation mode | Installed on 19-inch rack or inside the cabinet | |||
Maintenance mode | Front maintenance, support module grade change | |||
Protection level | IP20 | |||
INPUT Distribution | AC | DC | DC | |
Input mode | 380VAC three-phase | 120VDC to 340VDC | 120VDC to 340VDC | |
Input capacity | 1×100A/3P | 4×25A/2P | 1×63A/2P | |
Input frequency | 45~66Hz, rated value: 50Hz/60Hz | / | / | |
SPD | 20kA/40kA, 8/20μs | |||
OUTPUT Distribution | Output voltage | -42~-58VDC, rated value: -53.5VDC | -42~-58VDC, rated value: -54.5VDC | -42~-58VDC, rated value: -54.0VDC |
Maximum capacity | 24kW(Rectifier), 12KW(MPPT),6KW(Wind) | |||
Battery breakers | 3×250(125A/3P) | |||
Load breakers | LVLD:2×125A/1P, 1×16A/1P,1 reserve position LVBD:2×125A/1P, 2×6A/1P | |||
SPD | 20kA/40kA, 8/20μs | |||
Module | Rectifier module | MPPT module | Wind module | |
Input voltage | 85VAC~300VAC, rated 220VAC | 120VDC to 425VDC, rated 340VDC | 120VDC to 340VDC, rated 240VDC | |
Efficiency | ≥96% | ≥96% | ≥96% | |
Rated power | 3000W(176~300VAC) | 3000W(200~425VDC) | 3000W(200~340VDC) | |
Working temperature | -40℃~+75℃(fully output below 50℃) | |||
Dimension | 106.5mm(W)×286mm(D)×41.5mm(1U/H) | |||
Weight | ≤2kg | |||
Power factor | ≥0.99 | / | ||
THD | ≤5% | / | ||
Controller | Signal input | 4 AI(3 Battery temp., ambient temp) ,7 DI(SPD+ 6 common DI) | ||
Alarm output | 6 dry contact | |||
Communication port | RS485, SNMP | |||
Display mode | LCD | |||
Environment | Operating temperature | -40℃~+75℃ | ||
Storage temperature | -40℃~+75℃ | |||
Operating humidity | 5%~95%(non-condensing) | |||
Altitude | 0~3000m(If the altitude is within the range of 2000m to 3000m, the maximum operating temperature decreases by 1℃ as the altitude increases by 200m.) |